US Made Supply

✓ Verified

"Product and application as des..."

✓ Verified

"So far - love the product and ..."

✓ Verified

"very high quality. easy to app..."

Roofing & Roofs
Flat or Low Slope

NFPA 110: Level 1 vs Level 2 Emergency Power Systems

Standards for generators, transfer switches, and emergency power supply systems

Last updated: May 4, 2026

8 readers found this useful recently


Overview

NFPA 110 is the standard for emergency and standby power supply systems (EPSS): the rules for how generators, transfer switches, and fuel systems must be installed, tested, and maintained. It classifies systems as Level 1 (failure could cause loss of life) or Level 2 (less critical), and sets the testing schedule, fuel storage capacity, and room separation requirements. NFPA 110 does not decide which buildings need emergency power, that comes from NFPA 101, NFPA 99, or local building codes.

Critical Note: NFPA 110 does not determine which facilities require emergency power. Those requirements come from NFPA 101 (Life Safety Code), NFPA 99 (Healthcare Facilities), and local building codes. NFPA 110 specifies how to properly install and maintain the systems once required.

The standard applies to permanently installed emergency and standby power systems including generators, transfer equipment, controls, supervisory equipment, and associated electrical and mechanical auxiliary systems.

Level, Type, and Class Classifications

NFPA 110 uses three parameters to classify Emergency Power Supply Systems:

Level - Application Criticality

  • Level 1: Where failure could result in loss of human life or serious injuries
  • Level 2: Where failure is less critical to human life and safety

Type - Restoration Time

NFPA 110 Type classifications and restoration requirements
TypeRestoration TimeTypical Application
Type UUninterruptible (UPS)Critical computer systems
Type 1010 secondsEmergency lighting, life safety
Type 6060 secondsLess critical systems
Type 120120 secondsEquipment protection
Type MManual (no time limit)Portable generators

Class - Runtime Duration

  • Class 0.083: 5 minutes (UPS systems)
  • Class 0.25: 15 minutes
  • Class 2: 2 hours
  • Class 6: 6 hours
  • Class 48: 48 hours
  • Class X: Other time as required (typically 72-96 hours)

Level 1 vs Level 2 Requirements

Level 1 Systems (Life Safety Critical)

  • Emergency lighting for means of egress
  • Fire detection and alarm systems
  • Fire pumps
  • Elevators for high-rise buildings
  • Critical ventilation systems (smoke control)
  • Healthcare facility critical branches
  • Emergency communication systems

Level 2 Systems (Less Critical)

  • Heating and refrigeration systems
  • Communication systems (non-emergency)
  • Sewage disposal
  • Industrial processes
  • Data processing systems

Key Differences in Requirements

Comparison of NFPA 110 Level 1 and Level 2 emergency power requirements
RequirementLevel 1Level 2
Fuel Storage96 hours typicalAs specified
Testing FrequencyWeekly/MonthlyMonthly
Room Separation2-hour fire rating1-hour typical
Temperature Control40°F minimumPer manufacturer

System Components

A complete EPSS includes these essential components:

Energy Converters (EPS)

  • Prime Mover: Diesel, natural gas, or bi-fuel engines
  • Generator: Alternator producing electrical power
  • Cooling System: Radiator or heat exchanger
  • Exhaust System: Mufflers and emissions controls
  • Starting System: Batteries and charging system

Transfer Equipment

  • Automatic Transfer Switch (ATS): Transfers load between normal and emergency power
  • Bypass Isolation Switch: Allows ATS maintenance without interruption
  • Load Bank Connection: For testing without building load
  • Paralleling Gear: For multiple generator systems

Controls and Annunciation

  • Local and remote annunciator panels
  • Automatic starting controls
  • Battery monitoring systems
  • Remote monitoring capabilities
  • Load management controls

Fuel Systems & Storage

Fuel Storage Requirements

  • Main Tank Capacity: 133% of required runtime (safety factor)
  • Day Tank: 1 hour minimum supply at full load
  • Fuel Transfer: Automatic refill from main tank
  • Fuel Quality: ASTM-compliant diesel or natural gas
  • Fuel Polishing: Recommended for long-term storage
  • Natural Gas: Dual fuel connections where available

Fuel System Components

  • Fuel Pumps: Redundant pumps for Level 1 systems
  • Filters: Primary and secondary filtration
  • Water Separators: Remove moisture from fuel
  • Fill Connections: Accessible for emergency refueling
  • Fuel Polishing: Recommended for long-term storage
  • Natural Gas: Dual fuel connections where available

Generator yard spill response. NFPA 110 sets the performance and storage rules for the EPSS itself. The complementary spill-response equipment (drum spill pallets, oil-only sorbents, drip pans, drain covers) and the EPA SPCC eligibility test (1,320-gallon aboveground threshold) live alongside it. See Data Center Support-Area Safety for the generator-yard checklist.

Testing & Maintenance Requirements

NFPA 110 testing frequencies and load requirements
Test TypeLevel 1 FrequencyDurationLoad Requirements
No-Load TestWeekly5-10 minutesNone
Monthly TestMonthly30 minutesAvailable load
Annual TestAnnual4 hours100% nameplate
Triennial Test36 months4 hoursWith load bank
Transfer TestMonthlyComplete cycleActual loads

Maintenance Requirements

  • Weekly Inspection: Visual check of all systems
  • Oil & Filter Changes: Per manufacturer or oil analysis
  • Coolant System: Annual flush and refill
  • Battery Maintenance: Monthly specific gravity tests
  • Fuel Testing: Annual quality testing
  • Documentation: Written logs of all tests and maintenance

Installation Requirements

Location & Environment

  • Indoor Installation: Separate room with proper ventilation
  • Fire Rating: 2-hour separation for Level 1 systems
  • Temperature: Maintain minimum 40°F (Level 1), 32°F (Level 2)
  • Ventilation: Combustion air and cooling requirements
  • Working Space: 3 feet minimum around equipment
  • Outdoor Installation: Weather enclosures meeting Type ratings

Electrical Installation

  • Separate feeders for emergency loads
  • Proper grounding and bonding systems
  • Surge protection devices
  • Selective coordination of overcurrent devices
  • Remote annunciator in attended location
  • Integration with building management systems

Frequently Asked Questions

What is NFPA 110?

NFPA 110 is the Standard for Emergency and Standby Power Systems. It sets the installation, testing, and maintenance requirements for emergency power supply systems (EPSS), including generators, transfer switches, fuel systems, and controls. NFPA 110 does not determine which buildings require emergency power. That decision comes from NFPA 101 (Life Safety Code), NFPA 99 (Healthcare Facilities), and local building codes. The current edition is NFPA 110-2025.

What is the difference between NFPA 110 Level 1 and Level 2?

Level 1 systems serve loads where failure could cause loss of human life or serious injury, such as emergency lighting on means of egress, fire alarm, fire pumps, and high-rise elevators. Level 2 systems serve less critical loads such as heating, sewage disposal, and industrial processes. Level 1 has stricter rules: longer fuel storage, more frequent testing, 2-hour fire-rated room separation, and a 40 degrees F minimum room temperature. Level 2 typically requires 1-hour separation and monthly testing.

Can unrelated systems share the life safety generator room?

No. NFPA 110 requires the EPS room to be dedicated to the emergency power supply system and its directly supporting equipment. Equipment unrelated to the EPSS, such as building HVAC equipment, normal-power switchgear, or general-purpose storage, is not permitted in the same room. The separation rule protects the generator from a fire or failure originating in unrelated systems and keeps the room clear for testing and service access.

What is the NFPA 110 load bank testing requirement?

Level 1 generators that fail to reach 30 percent of nameplate kW during a monthly test must run an annual load bank test for 4 hours: 30 minutes at 25 percent, 30 minutes at 50 percent, and 3 hours at 75 percent of nameplate kW. Every 36 months, all Level 1 generators (regardless of monthly load) must run a triennial load bank test for 4 hours at full nameplate kW. Document every test in writing and keep records for the life of the system.

NFPA 110 Compliant Products

We don't have a curated product set for NFPA 110 yet. Search the catalog or browse related categories.

Search the catalog

Related Standards

Fire alarm systems require emergency power backup per NFPA 72 Fire Alarm Code. Fire pump controllers covered under NFPA 13 Sprinkler Systems also require emergency power connections.

For generator testing and inspection requirements by jurisdiction, see our Fire Inspection & Compliance Guide.

Hospitals, nursing homes, and ambulatory care facilities carry additional emergency-power obligations under CMS surveys and NFPA 99. See our sister site's healthcare fire-protection compliance overview.

Was this resource helpful?

Your feedback helps us improve our technical resources and guides.

Customer Support

Terms of ServicePrivacy PolicyShipping & DeliveryReturns & RefundsAccessibilityDMCAFAQs

Copyright © 2026 US Made, LLC. All Rights Reserved.

All content is for informational purposes only and does not constitute professional, legal, or compliance advice. Verify all requirements with the applicable standards and authorities.

Secure Payments

VisaMastercardAmerican ExpressDiscoverApple PayGoogle PayShop PayPayPal