US Made Supply

✓ Verified

"very high quality. easy to app..."

✓ Verified

"So far - love the product and ..."

✓ Verified

"Product and application as des..."

Roofing & Roofs
Flat or Low Slope

Photoluminescent Emergency Systems

Glow-in-the-dark exit signs, egress path marking, and low-location lighting requirements


Overview

Photoluminescent systems provide fail-safe emergency egress guidance without requiring electrical power or batteries. These systems absorb ambient light and emit a visible glow during power failures or smoke conditions, guiding occupants to safety. Required in high-rise buildings per IBC/IFC 1025 and increasingly adopted in critical facilities including data centers, hospitals, and industrial complexes.

Key Advantage: Photoluminescent systems require no electricity, batteries, or maintenance power. They charge from normal lighting (minimum 1 footcandle) and provide 90+ minutes of emergency illumination, making them ideal for backup to primary emergency lighting systems.

These systems are particularly effective in smoke conditions where traditional ceiling-mounted emergency lighting may be obscured. Low-location path marking at floor level remains visible below smoke layers, providing critical wayfinding when visibility is compromised.

UL 1994 Standard Requirements

UL 1994 establishes performance requirements for luminescent egress path marking systems:

  • Luminance Performance: Minimum 30 millicandellas per square meter at 10 minutes, 7 mcd/m² at 60 minutes, 5 mcd/m² at 90 minutes
  • Charging Requirements: Minimum 1 footcandle (10.8 lux) illumination on material surface for proper activation
  • Color Requirements: Yellow-green emission (520-535 nm wavelength) for optimal human eye sensitivity in darkness
  • Durability Testing: Resistance to salt spray, UV exposure, temperature cycling, and cleaning chemicals
  • Radioactivity: No radioactive materials permitted - must use strontium aluminate or similar non-radioactive phosphors
  • Service Life: Minimum 25-year expected service life with proper installation and maintenance

System Components

Complete photoluminescent egress systems include multiple components:

Exit Signs

  • UL 924 listed signs with 50-foot viewing distance in total darkness
  • 7-inch minimum letter height for new construction (IBC requirement)
  • Chevron directional indicators where required
  • Supplemental signs for "EXIT ONLY" or floor identification

Path Marking Components

  • Demarcation Lines: Continuous 1-inch minimum stripe at 6-8 inches above floor
  • Step Edge Marking: 1-inch stripe on horizontal and vertical surfaces of each step
  • Handrail Marking: Continuous marking on top surface or side of handrails
  • Obstacle Marking: Solid or dashed lines around floor-mounted obstacles
  • Door Frame Marking: 1-2 inch marking around exit door frames and hardware
  • Directional Signs: Chevron arrays at decision points and direction changes

High-Rise Building Requirements

IBC Section 1025 and IFC Section 1025 mandate photoluminescent exit path markings in high-rise buildings (occupied floor more than 75 feet above lowest level of fire department access):

  • Exit Stairways: All interior exit stairways and ramps must have photoluminescent marking
  • Exit Passageways: Corridors leading to exit discharge require path marking
  • Areas of Refuge: Marking required in areas of refuge and exterior exit stairways
  • Exceptions: Open, unenclosed stairwells and existing buildings where approved by AHJ
  • Integration: Must supplement, not replace, required emergency lighting systems
  • Inspection: Annual inspection required with documentation per NFPA 101

Data Center Applications

Critical facilities including data centers increasingly adopt photoluminescent systems for enhanced safety and compliance with industry standards:

Data Center Best Practice: Install photoluminescent floor striping in 2-inch widths along main egress routes, with directional arrows at 30-foot intervals. Mark all EPO stations, fire suppression controls, and electrical panels with photoluminescent borders for rapid identification during emergencies.

Performance Criteria

Photoluminescent system luminance requirements comparison
Time After ActivationUL 1994 MinimumNYC RS 6-1 MinimumTypical High-Performance
10 minutes30 mcd/m²30 mcd/m²150+ mcd/m²
30 minutes-10 mcd/m²50+ mcd/m²
60 minutes7 mcd/m²7 mcd/m²20+ mcd/m²
90 minutes5 mcd/m²5 mcd/m²10+ mcd/m²

Visibility Distances

  • Exit signs: 50-100 feet in total darkness depending on size
  • Path marking stripes: 15-20 feet visibility at floor level
  • Directional signs: 30 feet minimum recognition distance
  • Stair nosings: Visible from landing above and below

Installation Requirements

Proper installation ensures optimal performance and code compliance:

  • Surface Preparation: Clean, dry, smooth surfaces required; prime porous surfaces
  • Mounting Height: Demarcation lines 6-8 inches above finished floor (AFF)
  • Continuity: Maximum 4-inch gaps permitted for doorways and architectural features
  • Environmental Conditions: Install at 50-90°F with humidity below 85%
  • Charging Light Verification: Confirm minimum 1 fc illumination on all marked surfaces

Testing & Maintenance

Regular testing ensures continued compliance and performance:

Monthly Visual Inspection

  • Check for physical damage, delamination, or contamination
  • Verify continuous path marking without excessive gaps
  • Confirm adequate ambient lighting for charging (minimum 1 fc)
  • Document any deficiencies for correction

Annual Performance Testing

  • Conduct 90-minute darkness test after full charging period
  • Measure luminance at 10, 60, and 90-minute intervals
  • Verify visibility from maximum viewing distances
  • Test under smoke simulation conditions where required
  • Document results per NFPA 101 Chapter 7 requirements

Was this resource helpful?

Your feedback helps us improve our technical resources and guides.

Customer Support

Terms of ServicePrivacy PolicyShipping & DeliveryReturns & RefundsFAQs

Copyright © 2025 US Made, LLC. All Rights Reserved.