Backflow Preventers in Fire Protection Systems

Complete guide to backflow preventer testing, certification, and compliance requirements

Last updated: September 21, 2025


Overview

Backflow preventers are critical safety devices that protect potable water supplies from contamination by preventing water from flowing backward through fire protection systems. While not required by NFPA 13 for fire protection purposes, they are mandated by most water authorities to protect public health.

Insurance Impact: Many insurance carriers require documented backflow preventer testing as a condition of coverage. Failed or untested devices can result in denied claims following a fire incident.

Types of Backflow Prevention Assemblies

ASSE 1013

Reduced Pressure (RP)

Provides maximum protection against both backpressure and backsiphonage. Features a relief valve that discharges water if the downstream pressure exceeds upstream pressure by less than 2 PSI.

Common Applications:

  • High-hazard fire protection systems
  • Systems with chemical additives (antifreeze, foam)
  • Below-grade installations
  • Connections to booster pumps
ASSE 1015

Double Check (DC)

Contains two independently acting check valves providing redundant protection against backflow. Suitable for low to moderate hazard applications where RP assemblies are not required.

Common Applications:

  • Standard wet-pipe sprinkler systems
  • Fire department connections
  • Non-chemical fire suppression
  • Above-grade installations
ASSE 1048

Double Check Detector (DCDA)

Includes a bypass line with a water meter and smaller backflow assembly to detect unauthorized water use or small leaks while maintaining fire protection.

Common Applications:

  • Large commercial/industrial facilities
  • Where water theft detection is required
  • Systems requiring consumption monitoring
  • Campus-style fire protection networks
ASSE 1047

RP Detector (RPDA)

Combines the high-hazard protection of an RP assembly with the detection capabilities of a bypass meter. Required for high-hazard applications where water use monitoring is needed.

Common Applications:

  • Industrial facilities with chemical processes
  • Healthcare facilities with chemical suppression
  • High-hazard occupancies requiring metering
  • Systems with both chemical and water-based suppression

Testing Requirements

Test TypeFrequencyStandardRequired By
Visual Inspection (RP/RPD)WeeklyNFPA 25 Section 13.7.1.1Fire Code/Insurance
Main Drain Test (if BFP present)QuarterlyNFPA 25 Section 13.3.3.1Fire Code
Forward Flow TestAnnualNFPA 25 Section 13.7.2Fire Code
Backflow Prevention TestAnnualAWWA M14/Local CodeWater Authority
Internal Inspection5 YearsNFPA 25 Section 13.7.3Fire Code
After Repair/RelocationImmediateAll StandardsAll Authorities

Critical Testing Procedures

  • Weekly RP Inspection: Check that the differential-sensing valve relief port is not continuously discharging. Continuous discharge indicates first check valve failure or backpressure condition.
  • Quarterly Main Drain: When a backflow preventer and/or pressure reducing valves are installed between the water supply and main drain, test quarterly instead of annually per NFPA 25.
  • Forward Flow Test: Must be conducted at the system's required flow rate including hose stream allowance. Test connections per NFPA 13 are required. Exception: If fire pump test meets requirements, separate test not needed.
  • Backflow Test: Verifies check valves seal properly and relief valve opens at correct differential pressure (typically 2 PSI). Must use calibrated differential gauge test kit with annual calibration verification.
  • Documentation: Test reports must include tester certification number, test kit calibration date, specific pressure readings, and be retained for minimum one year after next test.

Tester Certification Requirements

Backflow preventer testing must be performed by certified testers who have completed approved training programs and maintain current certification through continuing education.

National Certifications

  • ASSE 5110: Backflow Prevention Assembly Tester Certification
  • ABPA: American Backflow Prevention Association Certification
  • AWWA: American Water Works Association Certification
  • TREEO: University of Florida Training Programs

Required Qualifications

  • 40-hour initial training course minimum
  • Hands-on testing experience requirement
  • Written and practical examinations
  • Annual gauge calibration verification
  • Continuing education (8-16 hours/2 years)
  • Professional liability insurance

State-Specific Requirements

California - Title 17

  • Testers must be certified by California-Nevada AWWA or approved equivalent
  • Annual testing required for all assemblies on fire protection systems
  • Test reports must be submitted to water supplier within 10 days
  • RP assemblies required for all connections with chemical additives
  • County health departments may impose additional requirements

Texas

  • Licensed by Texas Commission on Environmental Quality (TCEQ)
  • Customer Service Inspector (CSI) license required
  • Annual testing with 30-day report submission requirement
  • Local jurisdictions may require additional certifications

Florida

  • County-level certification programs (varies by county)
  • Department of Health approved training programs required
  • Annual testing with immediate hazard reporting
  • Contractor license may be required for repairs

Common Issues and Failures

Relief Valve Discharge (RP)

Continuous discharge from relief valve indicates:

  • Failed first check valve
  • Debris preventing check valve closure
  • Backpressure condition
  • Thermal expansion in downstream piping

Pressure Loss

Excessive pressure drop across assembly caused by:

  • Fouled check valves
  • Incorrect installation orientation
  • Undersized assembly for system demand
  • Closed or partially closed shutoff valves

Test Failures

Common reasons for failing annual tests:

  • Worn check valve seats and seals
  • Spring fatigue in check assemblies
  • Corrosion from water chemistry
  • Freeze damage in outdoor installations

Installation Issues

Problems from improper installation:

  • Insufficient clearance for testing
  • No test cocks or plugged test ports
  • Missing or inadequate drainage for relief valve
  • Installation in pit without proper drainage

NFPA Standards and Exceptions

Key NFPA 25 Requirements (2023 Edition)

  • Section 13.7.1.1: Reduced pressure assemblies shall be inspected weekly to ensure relief port is not continuously discharging
  • Section 13.7.2: All backflow preventers shall be forward flow tested annually at minimum flow rate of system demand
  • Section 13.3.3.1: Main drain test frequency increases to quarterly when backflow preventer is present between supply and drain
  • Section 13.7.3: Internal inspection required every 5 years to verify components move freely and seats/seals are in good condition

Testing Exceptions

  • Fire Pump Test Exception: If annual fire pump test has been conducted that includes flowing water through backflow preventer at required flow rate, separate forward flow test is not required
  • Drought Conditions: During official drought declarations, internal inspection of check valves may be substituted for forward flow test with AHJ approval
  • Electronic Monitoring: Continuously monitored pressure gauges may reduce inspection frequency with AHJ approval