UL 300: Kitchen Fire Suppression Systems
Fire testing requirements for pre-engineered commercial kitchen suppression systems
Last updated: September 21, 2025
Contents
Overview
UL 300 is the standard for fire testing of pre-engineered fire extinguishing systems for commercial cooking operations. Introduced in 1994 to address the higher temperatures of modern cooking oils, this standard ensures kitchen suppression systems can effectively combat grease fires in commercial kitchens.
Important: All pre-engineered kitchen suppression systems installed after November 21, 1994, must be UL 300 compliant. Systems installed before this date may still use dry chemical agents but should be upgraded for improved safety.
UL 300 systems use wet chemical agents specifically formulated to suppress high-temperature cooking oil fires through saponification, creating a foam blanket that prevents re-ignition.
Testing Requirements
UL 300 mandates rigorous fire testing to ensure system effectiveness:
- Temperature Testing: Systems must extinguish fires in cooking oils heated to auto-ignition temperature (approximately 680°F)
- Appliance Coverage: Testing on actual cooking appliances including deep fryers, ranges, griddles, and woks
- Re-ignition Prevention: Systems must prevent fire re-ignition after suppression
- Splash Testing: Agent discharge must not cause dangerous oil splashing
- Multiple Appliance Testing: Verification of simultaneous protection for multiple cooking appliances
- Duct and Plenum Testing: Confirmation of fire suppression in exhaust system components
System Components
UL 300 compliant systems include these essential components:
- Wet Chemical Agent: Potassium acetate, potassium carbonate, or potassium citrate solutions
- Storage Tanks: Stainless steel cylinders with pressure cartridges or stored pressure
- Detection System: Fusible links or electronic heat detectors rated for kitchen temperatures
- Distribution Piping: Stainless steel or chrome-plated piping resistant to corrosion
- Discharge Nozzles: Specifically designed for each appliance type and configuration
- Manual Pull Station: Remote manual activation capability
- Gas/Electric Shutoff: Automatic fuel and power shutoff to cooking equipment
Installation & Coverage
Proper installation ensures complete fire protection:
- Appliance Protection: Nozzles positioned per manufacturer specifications for each appliance
- Hood and Duct Coverage: Protection for exhaust hoods, filters, and duct entrance
- Overlapping Coverage: Ensures no gaps in protection zones between appliances
- Fusible Link Placement: Strategic positioning for rapid fire detection
- Clearance Requirements: Proper distances from cooking surfaces and heat sources
- Integration: Connection with building fire alarm and ventilation systems
Maintenance Requirements
Regular maintenance is crucial for system reliability and code compliance:
- Semi-Annual Inspection: Professional inspection every 6 months by certified technicians
- Monthly Visual Check: Staff verification of system components and manual pull stations
- Fusible Link Replacement: Replace when contaminated with grease or damaged
- Nozzle Caps: Regular cleaning and replacement to prevent clogging
- System Recharge: After any discharge, complete recharge and recertification required
- Documentation: Maintain inspection and service records for authority having jurisdiction
- Training: Staff training on manual activation and system operation
Compliance & Certification
To achieve UL 300 listing, manufacturers must:
- Submit complete systems for UL testing laboratory evaluation
- Pass all fire suppression performance tests
- Demonstrate consistent manufacturing quality control
- Provide detailed installation and maintenance manuals
- Undergo regular follow-up inspections at manufacturing facilities
- Display UL Listed mark on system components and documentation
UL 300 compliance is typically required by NFPA 96, International Mechanical Code (IMC), and local fire codes for all commercial kitchen fire suppression systems.