US Made Supply

✓ Verified

"Product and application as des..."

✓ Verified

"So far - love the product and ..."

✓ Verified

"very high quality. easy to app..."

Roofing & Roofs
Flat or Low Slope

UL 913: Intrinsically Safe Equipment

Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III, Division 1, and Class I, Zone 0 and 1 Hazardous Locations

Last updated: April 7, 2026


Overview

Every flammable gas, vapor, and dust has a minimum ignition energy (MIE), the smallest spark that can set it off. Intrinsic safety (IS) is the protection concept built around that fact: design the electrical circuit so that even under fault conditions, it physically cannot release enough energy to exceed the MIE of the surrounding atmosphere. No spark, no ignition, no explosion.

UL 913 is the North American standard that governs how intrinsically safe apparatus and associated apparatus are tested, evaluated, and certified. It covers equipment intended for use in Class I, II, and III, Division 1 hazardous locations, as well as Class I, Zone 0 and Zone 1 areas. The international equivalent is IEC 60079-11, which covers the same protection concept under the IECEx and ATEX certification systems used outside North America.

Intrinsic safety is the only protection method that is safe during normal operation, under expected faults, and under specific combinations of two simultaneous faults. That makes it the gold standard for instrumentation in the most dangerous classified areas. It is also the only technique that allows live maintenance in a Division 1 or Zone 0 area without a hot work permit.

In practical terms: If you are installing a temperature transmitter on a distillation column, a level sensor in a grain silo, or a gas detector on an offshore platform, the instruments and their wiring are almost certainly intrinsically safe circuits certified under UL 913 or IEC 60079-11.

How Intrinsic Safety Works

The core idea is energy limitation. Every component in the circuit is chosen and tested to guarantee that the total available electrical energy (from voltage, current, and stored energy in capacitors and inductors) stays below the minimum ignition energy of the target gas group, even when things go wrong.

UL 913 tests equipment under normal operation, one fault, and two simultaneous faults. The standard defines specific "safety factors" that multiply the test spark energy to provide margin. For Group A (acetylene) and Zone 0 applications, the safety factor is 1.5x. For Group D (propane, methane) in Division 1, it is 1.0x with specific fault conditions applied.

Energy Limiting Components

Three types of components do the work of keeping energy below the ignition threshold:

  • Current-limiting resistors cap the maximum current that can flow, even into a short circuit. They are sized so that the maximum power dissipation stays below the ignition threshold.
  • Voltage-clamping zener diodes shunt excess voltage to ground before it can build up. Redundant zeners (typically three in series) ensure that even if one fails shorted, the remaining diodes still clamp.
  • Energy-storage limiters restrict the capacitance and inductance in the circuit. Capacitors store electrical charge, inductors store magnetic energy, and both can release that energy as a spark. The standard sets maximum allowed values for each based on the gas group.

Ignition Curves

UL 913 uses ignition curves (voltage vs. current graphs for resistive circuits, and voltage vs. capacitance or current vs. inductance for reactive circuits) to determine safe limits. These curves are derived from extensive spark testing in standard gas/air mixtures. Equipment is certified for a specific gas group (A, B, C, or D) based on which curve it falls below.

Gas GroupRepresentative GasMIE (approx.)Relative Difficulty
AAcetylene0.017 mJHardest to protect
BHydrogen0.017 mJVery difficult
CEthylene0.065 mJModerate
DPropane / Methane0.25 mJMost common, easiest

Equipment rated for Group A is safe for all groups. Equipment rated only for Group D cannot be used in Group A, B, or C atmospheres.

Key point: Intrinsic safety does not mean the equipment will not break. It means that when it breaks, it cannot produce a spark hot enough to cause an ignition. The circuit is designed so that failure modes are safe.

Entity vs System Approval

There are two approaches to certifying intrinsically safe circuits, and the choice between them has major implications for how you specify, install, and maintain the equipment.

Entity Concept

Each device (barrier, field instrument, cable) is evaluated independently and given a set of "entity parameters" that describe its electrical characteristics. These parameters are published on the device label and in its control drawing. Any combination of entity-rated devices whose parameters are mathematically compatible can be connected without additional certification.

The key entity parameters are:

  • Vmax / Voc - Maximum voltage the device can accept (field device) or the open-circuit voltage the barrier can deliver
  • Imax / Isc - Maximum current the device can accept (field device) or the short-circuit current the barrier can deliver
  • Ci / Li - Internal capacitance and inductance of the field device (contributes to stored energy)
  • Ca / La - Maximum allowed external capacitance and inductance that the barrier can drive safely

For a valid entity combination: Voc must be less than or equal to Vmax, Isc must be less than or equal to Imax, and (Ci + Ccable) must be less than or equal to Ca, and (Li + Lcable) must be less than or equal to La.

System Approval

The entire circuit (barrier, field device, cable type, and cable length) is tested and certified as a single system. Nothing can be substituted without going back to the certifying body for re-evaluation. This approach is simpler for the end user because there are no parameter calculations, but it is rigid. Replacing a failed transmitter with a different model, or even a different cable length, requires new certification.

FactorEntity ConceptSystem Approval
FlexibilityHigh. Mix and match any compatible devices.Low. Must use the exact certified combination.
Engineering effortHigher. Must verify entity parameter compatibility.Lower. Just follow the control drawing.
Spare partsCan stock any compatible device.Must stock the exact certified model.
Initial certification costLower per device.Higher (whole system tested together).
DocumentationEntity parameter sheets for each device.Single control drawing for the whole loop.
Typical useProcess plants, refineries, general instrumentation.Specialized systems, OEM packages, mining equipment.

Practical advice: For most process plant instrumentation, the entity concept is the right choice. It gives you flexibility to change out transmitters, switch barrier brands, and adjust cable runs without recertifying the loop. System approval makes sense for packaged systems where the manufacturer controls every component.

IS Barriers

The barrier (also called an "associated apparatus") sits between the safe area (control room, marshalling cabinet) and the hazardous area (field). Its job is to limit the energy that can reach the hazardous area, regardless of what happens on the safe-area side. If a power supply fails, a wiring fault occurs, or someone accidentally connects 120V to the wrong terminal, the barrier prevents dangerous energy from reaching the field device.

Zener Barriers (Shunt-Diode Safety Barriers)

The simplest and cheapest type. A zener barrier contains zener diodes that clamp voltage, a series resistor that limits current, and a fuse that blows if the zener diodes fail. They work by shunting excess energy to ground, which means they require a dedicated IS ground connection with less than 1 ohm impedance.

The downside: that ground bond is critical. If the IS ground degrades (corrosion, loose connection, missing earth), the barrier cannot shunt fault energy, and the IS protection is compromised. Zener barriers also introduce a voltage drop into the loop (typically 1-2V), which can matter for long 4-20mA runs.

Galvanic Isolators

Galvanic isolators use transformers, optocouplers, or capacitive coupling to provide complete electrical isolation between the safe and hazardous sides. No common ground path exists, so there is no dependency on an IS ground. They also break ground loops that can cause measurement noise in 4-20mA circuits.

Modern installations overwhelmingly favor galvanic isolators despite their higher cost. The elimination of the IS ground requirement removes a maintenance burden and a common point of failure. Most barrier manufacturers now offer isolator modules that are pin-compatible replacements for their zener barrier lines.

FactorZener BarrierGalvanic Isolator
Cost per channel$30-80$80-250
Dedicated IS groundRequired (<1 ohm)Not required
Electrical isolationNone (shunt to ground)Full galvanic isolation
Voltage drop1-2V (zener + resistor)Minimal (powered device)
Ground loop noisePossibleEliminated
Power supplyPassive (no external power)Active (needs power supply)
Typical applicationSimple loops, retrofit, budget-constrainedNew construction, noise-sensitive, HART/digital

Warning: Zener barriers depend entirely on the integrity of the IS ground bus. If the ground connection fails or degrades above 1 ohm, the barrier cannot safely shunt fault energy. Inspect the IS ground termination during every scheduled maintenance cycle.

Marking and Labeling

UL 913 certified equipment carries a distinctive blue marking (a blue label, blue triangle, or blue nameplate field) that identifies it as intrinsically safe. This blue color coding is recognized across the industry and makes it easy for electricians to distinguish IS-rated equipment from general-purpose or explosionproof equipment.

What the Label Tells You

A typical UL 913 label includes the following information:

  • Classification - "Class I, Division 1, Groups A, B, C, D" tells you which gas groups and hazardous area division the device is rated for
  • Temperature code - T4 (135C), T3 (200C), etc. The maximum surface temperature of the device under fault conditions. Must be below the autoignition temperature of the target gas.
  • Entity parameters - Vmax, Imax, Ci, Li (for field devices) or Voc, Isc, Ca, La (for barriers). These numbers are what you use for entity compatibility calculations.
  • Control drawing number - The drawing that specifies allowed connections, cable types, cable lengths, and any restrictions.
  • Certification mark - UL listing mark, CSA mark, or FM approval mark from a Nationally Recognized Testing Laboratory (NRTL).

Common Temperature Codes

T-CodeMax Surface TempTypical Application
T1450C (842F)Hydrogen, very high AIT gases
T2300C (572F)Most common hydrocarbons
T3200C (392F)Gasoline vapors, some solvents
T4135C (275F)Acetaldehyde, diethyl ether
T5100C (212F)Carbon disulfide
T685C (185F)Rarely required in practice

The control drawing is the legal document. It specifies every allowed cable type, cable length, connected device, and configuration. When an inspector asks to see your IS documentation, the control drawing is what they want. Keep a copy at the barrier marshalling cabinet and in the maintenance office. Do not deviate from it.

Installation Requirements

Installing intrinsically safe wiring correctly is just as important as using certified equipment. The NEC (NFPA 70), Article 504, governs IS circuit installation in the United States. The fundamental principle: IS wiring must be kept physically separated from all non-IS wiring to prevent energy from non-IS sources from entering the IS circuit.

Wiring Separation Rules (NEC 504.30)

  • IS conductors must not be placed in any raceway, cable tray, or enclosure with non-IS conductors, unless separated by a grounded metal barrier or distance
  • IS wiring must be identified with blue color (blue insulation, blue cable jacket, or blue labeling at intervals)
  • IS terminal blocks must be separated from non-IS terminal blocks by at least 50mm (2 inches), or by a grounded metal partition
  • Junction boxes containing IS circuits must be labeled "INTRINSICALLY SAFE"

Cable Parameters

Cable capacitance and inductance per unit length add stored energy to the IS circuit. Longer cables mean more stored energy. The control drawing specifies the maximum allowed cable parameters (typically in pF/m and uH/m) and maximum cable length. When calculating entity compatibility, you must include the cable's contribution: total Ci + Ccable must not exceed the barrier's Ca, and total Li + Lcable must not exceed the barrier's La.

Cable TypeTypical CapacitanceTypical InductanceNotes
Standard instrument cable100-200 pF/m0.6-1.0 uH/mMost common for 4-20mA loops
Low-capacitance IS cable50-80 pF/m0.4-0.7 uH/mAllows longer runs for Group A/B
Fieldbus cable (FOUNDATION/HART)80-120 pF/m0.5-0.8 uH/mMust match fieldbus segment specs

Grounding

If you are using zener barriers, you need a dedicated IS ground bus with less than 1 ohm impedance to the plant grounding electrode. This ground must be separate from the instrument signal ground and the power ground. Galvanic isolators do not require this dedicated ground, which is one of their main advantages.

Warning: Mixing IS and non-IS wiring in the same conduit, cable tray, or junction box voids the IS rating and creates a potential ignition source. This is one of the most common installation violations found during audits. Blue wire color coding exists to prevent this, but it only works if everyone on the project follows it.

Industries Requiring IS Equipment

Any facility that processes, stores, or handles flammable gases, vapors, or combustible dusts will have areas classified as hazardous locations under the NEC. Intrinsically safe equipment is one of the approved protection methods for these areas. Here are the industries where you will most commonly encounter IS requirements.

IndustryCommon HazardsTypical ClassificationIS Equipment Used
Oil and gas (upstream)Methane, H2S, crude vaporClass I, Div 1, Group DGas detectors, level transmitters, pressure sensors
RefineriesHydrogen, hydrocarbon vaporsClass I, Div 1, Groups B/C/DTemperature transmitters, analyzers, flow meters
Chemical manufacturingSolvents, reactive gasesClass I, Div 1, Groups C/DProcess instruments, valve positioners
Grain handling/storageGrain dustClass II, Div 1, Group GLevel sensors, temperature probes, moisture meters
MiningMethane, coal dustMSHA-regulated (separate from NEC)Cap lamps, gas detectors, radios, proximity sensors
PharmaceuticalSolvent vapors (ethanol, IPA)Class I, Div 1, Group DProcess instruments in coating/drying areas
Wastewater treatmentMethane, H2SClass I, Div 1, Group DGas detectors, level transmitters in enclosed spaces
Painting and coatingSolvent vapors (MEK, toluene, xylene)Class I, Div 1, Group DBooth monitoring instruments, static grounding monitors
MRI suitesOxygen enrichment riskNot NEC-classified, but IS preferredPatient monitoring, infusion pumps, communication devices

Mining note: MSHA (Mine Safety and Health Administration) has its own certification requirements (30 CFR Part 18 and Part 22) that go beyond the NEC. Equipment used underground in coal mines must carry MSHA approval, not just a UL 913 listing. Some manufacturers carry dual UL/MSHA approvals.

Inspection and Maintenance

IS equipment requires regular inspection to maintain its protection integrity. Unlike general-purpose equipment, the safety of an IS circuit depends on the precise electrical characteristics of every component in the loop, including the cable. Changes that would be harmless in a regular circuit (swapping a transmitter for a different model, extending a cable run) can compromise IS protection.

Inspection Checklist

  • Barrier integrity - Verify that barriers show no signs of overheating, discoloration, or physical damage. Check fuse continuity on zener barriers.
  • Ground continuity (zener barriers) - Measure the IS ground bus impedance. It must remain below 1 ohm. Check all terminations for corrosion or looseness.
  • Cable condition - Look for damage to blue IS cables, especially at penetrations, cable trays, and junction boxes. Verify that blue color coding is visible and legible.
  • Wiring separation - Confirm that IS wiring has not been mixed with non-IS wiring since the last inspection. This happens more often than you would expect, usually during unrelated maintenance work.
  • Label legibility - Equipment labels (blue marking, entity parameters, temperature code, control drawing number) must be readable. Replace or re-mark any faded labels.
  • Control drawing availability - A current copy of each control drawing should be accessible at the barrier marshalling cabinet and in the maintenance office. If a drawing is missing, obtain a replacement from the manufacturer before doing any work on that loop.

Device Replacement

Replacing a field device in an IS loop is not the same as swapping a transmitter in a general-purpose circuit. Before installing a replacement device:

  • Verify the replacement device's entity parameters against the control drawing
  • Confirm the Vmax of the replacement is greater than or equal to the barrier's Voc
  • Confirm the Imax of the replacement is greater than or equal to the barrier's Isc
  • Verify that (Ci of new device + Ccable) does not exceed the barrier's Ca
  • Verify that (Li of new device + Lcable) does not exceed the barrier's La
  • Check that the temperature code is appropriate for the gas group at the installation location
  • Update the control drawing if the replacement is a different model than the original

Warning: IS equipment cannot be field-repaired in the same way that general-purpose instruments can. Opening an IS device, replacing internal components, or modifying its circuitry can change the energy-limiting characteristics that make it safe. Repairs must be performed by the manufacturer or by a facility following the manufacturer's documented repair procedures.

Frequently Asked Questions

What does the blue label on intrinsically safe equipment mean?

The blue color (or blue triangle marking) identifies equipment certified as intrinsically safe. It tells installers and inspectors that the device has been evaluated under UL 913 or IEC 60079-11 and is approved for use in hazardous locations. Blue is used universally across the industry for IS identification, from equipment labels to wiring insulation to terminal blocks.

Can I use any IS-rated device with any IS barrier?

Only if both use entity parameters and the numbers are compatible. The field device's Vmax must be greater than or equal to the barrier's Voc (open circuit voltage), and the same applies for Imax vs. Isc, and the total circuit capacitance and inductance (including cable) must fall within the barrier's Ca and La. If either device has system-only approval, you must use the exact combination specified in the control drawing.

Is intrinsic safety the only option for Division 1 areas?

No. Explosionproof (XP) enclosures (UL 1203) and purged/pressurized equipment (NFPA 496) are also allowed in Division 1. Intrinsic safety is preferred for low-power instruments and portable devices because it is lighter, cheaper, and allows live maintenance. Explosionproof is typically used for motors, large junction boxes, and other higher-power equipment.

Can I repair intrinsically safe equipment in the field?

Generally no. Field modifications or repairs can change the energy-limiting characteristics that make the device safe. Even replacing a battery with a different model can void the certification. Repairs must be done by the manufacturer or a facility following the manufacturer's documented repair procedures. The certification applies to the device as built by the manufacturer, not as modified in the field.

What is the difference between UL 913 and IEC 60079-11?

UL 913 is the North American standard, tested and certified by a Nationally Recognized Testing Laboratory (NRTL) such as UL, CSA, or FM. IEC 60079-11 is the international standard used under the IECEx and ATEX certification systems. The technical requirements are similar (both use the same ignition curve data and fault-count methodology), but the certification marks and approval processes differ. Equipment certified to one standard may not automatically be accepted under the other without additional evaluation by the local authority.

Do intrinsically safe flashlights exist?

Yes. Several manufacturers make flashlights certified to UL 913 for use in Class I/II Division 1 locations. They use current-limited LED circuits and low-energy battery configurations designed so that even a dead short or dropped impact cannot release ignition-level energy. When shopping for one, check the UL listing for the specific gas groups and division rating, and look at the ANSI FL-1 ratings for light output performance.

Related Standards

NFPA 70 Hazardous Location Classifications

Class/Division and Zone classifications that determine where IS equipment is required

ANSI FL-1 Flashlight Performance

Standardized performance metrics for portable lighting including IS-rated flashlights

OSHA 1910.106 Flammable Liquids

Flammable liquid storage rules that trigger hazardous area classification

NFPA 70E Electrical Safety

Electrical workplace safety, PPE, and approach boundaries

Was this resource helpful?

Your feedback helps us improve our technical resources and guides.

Customer Support

Terms of ServicePrivacy PolicyShipping & DeliveryReturns & RefundsFAQs

Copyright © 2026 US Made, LLC. All Rights Reserved.

All content is for informational purposes only and does not constitute professional, legal, or compliance advice. Verify all requirements with the applicable standards and authorities.

Secure Payments

VisaMastercardAmerican ExpressDiscoverApple PayGoogle PayShop PayPayPal