Rated 4.9/5 by verified buyers

US Made Supply
/
Roofing & Roofs
Flat or Low Slope

NFPA 101: Life Safety Code

Means of egress, emergency lighting, exit signs, and occupancy requirements for commercial and institutional buildings

Last updated: July 12, 2026

15 readers found this useful recently


Overview

NFPA 101, the Life Safety Code, is the most widely adopted code in North America for protecting building occupants from fire and related hazards. First published in 1927, it establishes minimum requirements for means of egress design, emergency lighting, exit marking, fire protection features, and interior finish, organized by occupancy type so that a hospital, a warehouse, and an assembly hall each get requirements scaled to their actual risk.

The current edition is NFPA 101-2024, updated on a three-year cycle. NFPA 101 is adopted statewide in over 40 US states either directly or through reference in the state building or fire code. CMS (Centers for Medicare & Medicaid Services) mandates NFPA 101 for all healthcare facilities participating in Medicare/Medicaid, making it the controlling code for hospitals, nursing homes, and ambulatory surgical centers nationwide.

Key concept: NFPA 101 treats egress as a three-part system: exit access (the path from any occupied point to an exit), exit (the protected path itself, such as an enclosed stair, exterior door, or horizontal exit), and exit discharge (from the exit to the public way). Requirements differ at each stage because the level of protection differs.

2024 Edition Changes

The 2024 edition introduced several notable updates from the 2021 cycle:

  • Portable fire extinguishers now required in both new AND existing assembly occupancies (§12.3.5, §13.3.5), a notable shift toward early-intervention equipment
  • Carbon monoxide detection scope expanded: now applies in certain existing educational and day-care areas, and in new health care, ambulatory health care, and detention/correctional occupancies (§9.8, designed to NFPA 72 Ch. 17)
  • Interior exit discharge allowance increased from 50% up to 75% of required exits where the building is sprinklered and 1-hour fire barriers separate the discharge route (§7.7.2)
  • Modular rooms / sleep pods addressed for the first time: definitions in Ch. 3, UL 962 listing required, cannot reduce egress capacity
  • Inflatable amusement devices brought into scope (ASTM F2374, NFPA 701)
  • Alternate Care Sites (ACS) permitted in Chs. 18/19 with an approved fire emergency plan and alternate construction provisions (Annex D guidance)
  • Updated health care suite arrangement provisions (the 40,000 sq ft smoke-compartment allowance itself dates to the 2018 edition, not 2024)

CMS adoption gap: CMS still enforces the 2012 edition of NFPA 101 for Medicare/Medicaid surveys, adopted via the 2016 final rule (effective July 2016; surveys to the 2012 edition began November 2016). CMS has not adopted the 2018, 2021, or 2024 editions. Healthcare facilities must comply with the 2012 edition for CMS surveys, even if their state or local authority enforces a newer edition. This dual-compliance situation means healthcare projects often need to satisfy both the current state-adopted edition and the CMS-mandated 2012 edition.

Means of Egress (Chapter 7)

Chapter 7 is the heart of NFPA 101. It defines how occupants move from any point in a building to safety outside. Occupancy-specific chapters (12-42) modify these base requirements, but Chapter 7 sets the floor.

Travel Distance & Dead-End Limits

Travel distance is measured from the most remote occupied point to the nearest exit. Dead-end corridors force occupants to backtrack, increasing evacuation time. Limits vary by occupancy and sprinkler protection.

OccupancyMax Travel DistanceMax Dead-End
Assembly (sprinklered)250 ft20 ft
Business (sprinklered)300 ft50 ft
Educational (sprinklered)200 ft20 ft
Healthcare (sprinklered)200 ft30 ft
Mercantile (sprinklered)250 ft50 ft
Industrial, general (sprinklered)250 ft50 ft
High hazard75 ft0 ft (none permitted)

Non-sprinklered buildings have shorter limits. Always check the occupancy-specific chapter for your building type.

Calculating Occupant Load (§7.3.1.2)

Before you can size exits you need the occupant load. NFPA 101 §7.3.1.2 sets the occupant-load factor by use (floor area per person), and §7.3.3 sets the egress capacity per occupant. NFPA 101's factor table is not identical to the IBC's — it uses a smaller area-per-person for some uses — so confirm the factor in whichever code your AHJ enforces. For a quick estimate, the occupant-load calculator on our IBC Chapter 10 page walks the math (verify against the NFPA 101 factor when NFPA 101 governs).

Number of Exits

Every floor with occupants needs at least two exits, with limited exceptions for small occupant loads. Exits must be remote from each other. The separation distance between two exits must be at least one-half the maximum overall diagonal of the building or area served (one-third if the building is fully sprinklered).

Occupant LoadMinimum Exits Required
1-5002
501-1,0003
Over 1,0004

Single-exit allowance. §7.4.1.1 sets two means of egress as the floor; specific occupancy chapters permit a single exit only under narrow conditions. Common thresholds in the 2024 edition:

  • New Business: a single exit is permitted only in limited cases — e.g., a building of three or fewer stories with no more than 30 occupants per story and ≤100 ft travel to the outside (§38.2.4.4), or a sprinklered two-story single-tenant building with ≤100 ft travel (§38.2.4.6)
  • New Mercantile (§36.2.4.4): a single means of egress is permitted only in a Class C store (≤3,000 sq ft gross, one story) where travel to the exit or mall is ≤100 ft and the store and communicating levels are sprinklered
  • New Apartment (§30.2.4): single exit permitted only for buildings of no more than four stories with no more than four dwelling units per story, fully sprinklered, with limited travel distance (≤35 ft from a unit door to the exit) and 1-hour-rated stair and corridor enclosure
  • Assembly (§12.2.4 / §13.2.4): two exits required for any space with occupant load ≥ 50; three required at >500; four at >1,000

Always verify the specific single-exit conditions in the AHJ's adopted edition. The trigger occupant load and travel-distance limits change between editions.

Door & Stair Requirements

  • Exit doors must swing in the direction of egress travel when serving 50 or more occupants
  • Minimum clear door width: 32 inches (34-inch door leaf typical to achieve this)
  • Panic hardware (push bars) required on exit doors serving assembly or educational occupancies with 100+ occupants, and high-hazard contents areas
  • Fire exit hardware required when the door is in a fire-rated assembly and panic hardware is needed; where its listing calls for it, the same assembly also needs intact fire door gasketing for smoke and draft control, which is separate from its fire rating
  • Stair width: minimum 44 inches where serving 50+ occupants (36 inches for fewer)
  • Maximum riser height: 7 inches; minimum tread depth: 11 inches
  • Handrails required on both sides of stairs, 34-38 inches above tread nosing

Controlled Egress Locks

Section 7.2.1.5.1 requires that doors in a means of egress be operable from the egress side without keys, tools, or special knowledge. However, NFPA 101 permits several special locking arrangements under strict conditions. The two most common are:

Lock TypeRelease MechanismConditions
Delayed egress (7.2.1.6.1)Holds door up to 15 seconds after pushBuilding protected throughout by supervised automatic sprinklers or fire detection (per the occupancy chapter); releases on alarm or power failure; signage required
Access-controlled (7.2.1.6.2)Releases immediately on sensor/push barReleases on fire alarm, power failure, or loss of communication with access control; signage required

Common violation: Locking or chaining exit doors. A standard deadbolt or padlock on an exit door is generally prohibited unless a specific code exception applies. Delayed-egress and sensor-release (access-controlled) locks are the most common permitted arrangements, and only when all conditions (sprinkler protection, fire alarm integration, signage) are met.

Emergency Lighting (Section 7.9)

Emergency lighting must activate automatically when normal power fails and illuminate the path to exits so occupants can evacuate safely. Section 7.9 sets the baseline; occupancy chapters specify where it is required.

Duration & Illumination

ParameterRequirement
Minimum duration1.5 hours (90 minutes) on battery or generator
Initial illuminationAverage of 1.0 fc (10.8 lux) along the path of egress
Minimum at any pointNot less than 0.1 fc (1.1 lux)
End-of-duration declineMay decline to 60% of initial (0.6 fc average, 0.06 fc minimum at any point) at 90 minutes
Uniformity ratioMax-to-min must not exceed 40:1
Power transfer time10 seconds maximum from normal power loss

Required Locations

  • Designated exit stairs and smoke-proof enclosures
  • Aisles, corridors, and ramps that are part of the exit access
  • Passageways and tunnels used as exits
  • Exit discharge areas from the building to the public way
  • All exit access in assembly occupancies for 300+ occupants
  • Interior exit discharge in buildings over 75 feet in height
  • Elevator cabs and lobbies in high-rise buildings

Exit Signs (Section 7.10)

Sign Specifications

  • Word "EXIT" in plainly legible letters in a distinctive color that contrasts with the background — red and green are the most common, though NFPA 101 specifies contrast and legibility rather than a fixed color
  • New signs: letters at least 6 inches high with 3/4-inch minimum stroke width
  • Existing signs: letters at least 4 inches high permitted where already installed
  • NFPA 170 pictogram signs (running-man symbol) permitted when approved by the AHJ
  • Directional indicators (chevron-type) required when the exit direction is not immediately apparent

Placement

  • Required wherever the exit or the path to an exit is not immediately visible; main exterior exit doors that are obvious and clearly identifiable are excepted
  • Viewing distance must not exceed the sign's listed viewing distance or 100 feet, whichever is less
  • Bottom of sign not more than 80 inches (6 ft 8 in) above the top of the door opening when mounted above a door
  • Floor-proximity signs: 6-18 inches above floor (required in some occupancies for smoke conditions)
  • No decorations, furnishings, or equipment shall obstruct visibility of exit signs

Equipment standard: Emergency lighting units and internally illuminated exit signs must be listed to UL 924 by a nationally recognized testing laboratory (NRTL). UL 924 governs construction, performance, and testing of the equipment itself, while NFPA 101 governs where it must be installed and how it must perform in the building.

Illumination Types

TypeRequirementNotes
Externally illuminatedMinimum 5 fc (54 lux) at sign faceMust be on emergency power circuit
Internally illuminatedListed to UL 924LED with integral battery backup is most common
PhotoluminescentListed to UL 924Requires continuous charging light source; no battery needed
Self-luminousApproved by AHJTritium-based; no external power; 10-20 year life

Occupancy Classifications

NFPA 101 assigns requirements based on occupancy classification, not construction type. Chapters 12-42 cover specific occupancies in pairs: one chapter for new construction, one for existing buildings.

OccupancyChaptersEmergency LightingKey Egress Notes
Assembly12-13Required in all assembly spacesPanic hardware at 100 occupants; main exit sized for 1/2 occupant load
Educational14-15Required in stairs, corridors, windowless areasClassroom doors may latch from inside; 150 ft travel distance
Healthcare18-19Essential electrical system per NFPA 99Defend-in-place strategy; smoke compartments; corridor smoke partitions
Detention22-23Required throughoutLocked doors permitted with staff-controlled release; smoke compartments
Hotels/Dormitories28-29Required in corridors, stairs, lobbiesGuest room doors self-closing and self-latching
Business38-39Required per \u00a738.2.9 (new: 3+ stories, 50+ occupants above/below the level of exit discharge, or 300+ total) / \u00a739.2.9 (existing: 3+ stories, 100+, or 1,000+)Single exit only in limited cases \u2014 e.g., 3 or fewer stories at 30 or fewer occupants per story, travel to the outside within 100 ft (§38.2.4.4)
Industrial40Required in high hazard areas and egress pathsSpecial provisions for high hazard contents; reduced travel distances
Storage42Required (§42.2.9), with a natural-illumination exception where approvedHigh-piled storage may trigger additional requirements

Mandatory Life Safety Evaluation

A life safety evaluation (LSE) is a written analysis of the building, the occupancy, and the planned event or use, prepared by a registered or qualified designer and approved by the AHJ. It documents how non-fire hazards (overcrowding, hazardous activities, panic) and fire hazards interact with the means of egress and the protection systems. NFPA 101 calls one out only for specific occupancy types and configurations, most commonly large or special-configuration assembly occupancies.

When NFPA 101 requires a life safety evaluation

In the 2024 edition, the requirement sits in §12.4.1 (new assembly) and §13.4.1 (existing assembly), with related rules in §12.4.2 / §13.4.2 for specific seating configurations. The trigger conditions most often cited:

  • Assembly occupancies with smoke-protected assembly seating (§12.4.2 / §13.4.2): stadiums, arenas, indoor sports venues
  • Outdoor assembly with permanent or movable seating, where the occupant load and the venue characteristics warrant a documented analysis
  • Special amusement buildings (§12.4.8 / §13.4.8): go-kart tracks, haunted houses, escape rooms, and similar attractions where occupants may be intentionally disoriented
  • Stadiums with grandstands, bleachers, or folding-and-telescopic seating above defined occupant-load thresholds
  • Any assembly occupancy where the AHJ requires one based on use, occupant load, or arrangement

The exact occupant-load triggers are edition- and configuration-specific. Always confirm against the AHJ's adopted edition using the NFPA 101 free-access text.

What a life safety evaluation must address

  • Nature of the events held in the building (concerts, sports, exhibits, performances) and the occupant profile (age, mobility, familiarity with the venue)
  • Occupant load by space and by configuration, including standing-room and movable seating
  • Means of egress capacity, travel distance, common-path, and dead-end against the occupancy chapter limits
  • Crowd management, including queuing, ushering, and access/egress at peak load
  • Fire protection features: detection, alarm, communications, sprinklers, smoke control, emergency lighting, exit marking
  • Structural and operational provisions for power loss, alarm conditions, and shelter-in-place where applicable
  • Documented review and approval by the AHJ before initial occupancy and at any change of use, configuration, or occupant load

Common pitfall: a life safety evaluation is not a one-time document. Substantial changes in occupant load, seating configuration, or planned event type can re-trigger the requirement. Re-evaluate before any change in use, before adding or removing seating, and at any change of ownership or operator that changes the occupant profile.

Interior Finish & Fire Protection (Section 10.2)

Interior finish refers to the exposed surface of walls, ceilings, and floors within a building. NFPA 101 regulates these materials because they directly affect how fast fire and smoke spread through occupied spaces.

Wall & Ceiling Classifications

Interior wall and ceiling finish is classified by flame spread index (FSI) and smoke developed index (SDI) per ASTM E84 (tunnel test):

ClassFlame Spread IndexSmoke Developed IndexTypical Use
Class A0-250-450Exit enclosures, corridors, lobbies
Class B26-750-450Exit access corridors, rooms
Class C76-2000-450Rooms and other areas (where permitted)

Floor Finish

Interior floor finish is classified by critical radiant flux per ASTM E648 (radiant panel test):

  • Class I: Minimum 0.45 W/cm² critical radiant flux. Commonly required in exit enclosures and exit access corridors; the occupancy chapter sets the exact class.
  • Class II: Minimum 0.22 W/cm² critical radiant flux. Permitted in rooms and other areas.

Alternative test method: Materials that pass NFPA 286 (Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth) may be accepted in place of the ASTM E84 classification when they meet NFPA 101's specific acceptance criteria. NFPA 286 is a full-room-scale fire test that is more representative of real fire conditions, especially for thermoplastic materials where the tunnel test has known limitations.

Common Violations & Enforcement

Enforcement of NFPA 101 falls to the authority having jurisdiction (AHJ), which may be a state fire marshal, local fire department, or CMS surveyors for healthcare facilities. The violations below consistently appear at the top of inspection and survey deficiency lists.

Top Healthcare Survey Deficiencies (CMS K-Tags)

CMS surveys of hospitals, nursing homes, and ambulatory surgical centers routinely flag these NFPA 101 violations:

ViolationWhat Inspectors Find
ABHR dispenser placementExceeding the 1.2 L maximum individual dispenser capacity or the 10-gallon aggregate per smoke compartment, or placement above ignition sources
Hazardous area separationStorage rooms, labs, and soiled utility rooms lacking required fire resistance rating or sprinkler protection
Sprinkler maintenanceMissing or overdue NFPA 25 inspections, obstructed sprinkler heads, inadequate 18-inch clearance below sprinklers
Exit signs & emergency lightingNon-functional signs, burned-out emergency lights, no monthly/annual test documentation
Corridor obstructionEquipment, carts, or storage reducing required egress corridor width
Exit door hardwareDoors that don't latch, delayed egress systems not functioning, hardware that impedes egress
Electrical deficienciesExtension cord misuse, power strip daisy-chaining, blocked electrical panel access

General Commercial & Assembly Issues

  • Locked, blocked, or chained exit doors (the single most dangerous violation)
  • Propped-open fire doors that should be self-closing, or a door closer that no longer latches the door
  • Missing or non-functional emergency lighting with no testing records
  • Missing, expired, or unmaintained portable fire extinguishers (monthly visual inspection records and annual maintenance tags), or units mounted outside the required mounting height and travel-distance limits
  • Exceeding posted occupant load in assembly spaces
  • Furniture or displays reducing exit access aisle width below the minimum
  • Exit signs obscured by decorations, banners, or new construction

Testing & Maintenance

Section 7.9.3 requires periodic testing of emergency lighting equipment. Building owners must maintain written records and make them available to the authority having jurisdiction (AHJ) on request.

TestFrequencyDurationWhat to Document
Functional testMonthly (30-day intervals)30 seconds minimumDate, pass/fail, deficiencies found
Full duration testAnnually1.5 hours (90 minutes)Date, illumination maintained, battery condition
Exit sign inspectionMonthlyVisual checkSign visible, illuminated, not obstructed
Battery replacementAs needed per test resultsN/ADate replaced, battery type, unit location

Self-testing equipment: NFPA 101 permits self-testing and self-diagnostic battery units that automatically perform the monthly 30-second test and indicate failures. These units still require the annual 90-minute test and periodic visual verification that the self-test indicator is functioning.

NFPA 101 vs IBC

Many jurisdictions adopt the International Building Code (IBC) for new construction and reference NFPA 101 separately. While both codes address life safety, they differ in scope and structure.

AttributeNFPA 101IBC
ScopeLife safety and egress onlyComprehensive building code (structural, fire, egress, plumbing, etc.)
Existing buildingsCovered in occupancy chapters (odd-numbered)Handled by separate IEBC
HealthcareMandated by CMS for Medicare/Medicaid facilitiesNot mandated by CMS
Performance-based designChapter 5 provides a full PBD frameworkLimited alternative methods provisions
Emergency lighting duration90 minutes90 minutes (IBC Section 1008)
Exit sign letter height (new)6 inches minimum6 inches minimum
Panic hardware thresholdAssembly or educational at 100+ occupantsGroup A or E at 50+ occupants (§1010.2.9)
Elevator evacuationOccupant evacuation elevators (OEE) per §7.14Occupant evacuation elevators per IBC Section 3008

When both codes apply to a project, the more restrictive requirement governs. For Medicare/Medicaid healthcare projects, CMS enforces NFPA 101 for certification surveys in addition to any state or local building and fire codes that also apply.

Frequently Asked Questions

Does NFPA 101 apply to single-family homes?

Rarely. NFPA 101 has a dedicated chapter for one- and two-family dwellings (Chapter 24), but it is seldom the adopted code for single-family homes. Most jurisdictions rely on the IRC (International Residential Code) for single-family residential life safety.

When is panic hardware required versus fire exit hardware?

Panic hardware (push bars that release the latch) is required on exit doors in assembly and educational occupancies with 100+ occupants, and high-hazard areas. If that door is also in a fire-rated wall or opening, you need fire exit hardware, which is panic hardware that additionally carries a fire listing. The fire listing means the latch stays engaged during a fire to maintain the fire barrier. Standard panic hardware retracts all latching points, which defeats the fire rating.

Can existing buildings be grandfathered from NFPA 101 requirements?

Partially. NFPA 101 has separate chapters for existing buildings (the odd-numbered occupancy chapters), which generally allow conditions that were compliant when built. However, certain requirements are retroactive regardless of when the building was constructed: working fire alarms, functional emergency lighting, and unobstructed egress paths. A change of occupancy classification triggers full compliance with the new occupancy chapter.

What is defend-in-place and where does NFPA 101 require it?

Defend-in-place means occupants are relocated to an adjacent smoke compartment on the same floor instead of evacuating the building. NFPA 101 requires this strategy for healthcare (Chapters 18-19) and detention (Chapters 22-23) occupancies, where occupants cannot self-evacuate. These chapters require smoke barriers to create compartments, minimum compartment sizes, and direct access between compartments so patients or inmates can be moved horizontally away from smoke or fire without using stairs.

Which edition of NFPA 101 does CMS enforce?

CMS enforces the 2012 edition of NFPA 101 for Medicare/Medicaid healthcare facility surveys, adopted via the 2016 final rule (effective July 2016; surveys began November 2016). CMS has not adopted the 2018, 2021, or 2024 editions. If your state fire code references a newer edition, you must comply with both the state-adopted edition and the CMS-mandated 2012 edition.

Does NFPA 101 address active shooter or hostile events?

Not directly. NFPA 101 does not have a standalone chapter on active shooter/hostile events. That topic is covered by NFPA 3000 (Standard for an Active Shooter/Hostile Event Response Program). However, the door hardware provisions in Section 7.2 were influenced by these concerns. NFPA 101 prohibits hardware that prevents egress from the corridor side but allows classroom security function locks that can be locked from inside the room while still allowing egress.

What is the difference between NFPA 101 and NFPA 5000?

NFPA 101 covers life safety only: egress, lighting, fire protection features, and interior finish. NFPA 5000 (Building Construction and Safety Code) is NFPA's comprehensive building code that covers structural requirements, plumbing, mechanical, and electrical in addition to life safety. NFPA 5000 is an alternative to the IBC, but has much lower adoption. Most jurisdictions that adopt NFPA 101 pair it with the IBC rather than NFPA 5000.

What is NFPA 101?

NFPA 101, the Life Safety Code, is a model code published by NFPA that sets minimum requirements for the design, construction, operation, and maintenance of buildings to protect occupants from fire, smoke, and similar hazards. It applies to both new and existing buildings, with paired chapters covering each, and is adopted statewide in over 40 US states either directly or by reference. The current edition is NFPA 101-2024.

When does NFPA 101 require two means of egress?

Section 7.4.1.1 sets two means of egress as the floor for any balcony, mezzanine, story, or portion of a story serving an occupant load above the occupancy chapter's single-exit threshold. Common 2024-edition triggers: Business permits a single exit only in limited cases — for example, three or fewer stories with no more than 30 occupants per story and travel to the outside within 100 ft (§38.2.4.4), or a sprinklered two-story single-tenant building within 100 ft of travel (§38.2.4.6); Assembly requires two exits at any space with occupant load ≥ 50 (§12.2.4 / §13.2.4); Mercantile permits a single exit only for small street-floor stores under specific limits. Three exits are required at >500 occupants and four at >1,000 (§7.4.1.2).

When does NFPA 101 require a mandatory life safety evaluation?

A life safety evaluation is required for certain assembly occupancies under §12.4.1 (new) and §13.4.1 (existing), with related rules in §12.4.2 / §13.4.2 for specific seating configurations. The most common triggers are smoke-protected assembly seating (stadiums, arenas), outdoor assembly with permanent or movable seating, special amusement buildings (§12.4.8 / §13.4.8), and grandstands or bleachers above occupant-load thresholds. The AHJ may require one in any assembly occupancy based on use, occupant load, or arrangement. Confirm specific triggers against the AHJ's adopted edition.

NFPA 101 Compliant Products

View all 23
Von Duprin 22EO6893 22 Series 3' Rim Exit Device 689 Aluminum Finish

Von Duprin 22EO6893 22 Series 3' Rim Exit Device 689 Aluminum Finish

$672.00

Von Duprin 3547AEO26D3 3' Concealed Vertical Rod Narrow Exit Device Smooth Case, 626 Satin Chrome Finish

Von Duprin 3547AEO26D3 3' Concealed Vertical Rod Narrow Exit Device Smooth Case, 626 Satin Chrome Finish

$3,637.00

Von Duprin 3547AEO3133 3' Concealed Vertical Rod Narrow Exit Device Smooth Case, 710 Dark Bronze Finish

Von Duprin 3547AEO3133 3' Concealed Vertical Rod Narrow Exit Device Smooth Case, 710 Dark Bronze Finish

$3,145.00

Von Duprin 8827L10B3LHR 3' Surface Vertical Rod Push Bar Exit Device with Left Hand Reverse Lever Trim 613 Oil Rubbed Bronze Finish

Von Duprin 8827L10B3LHR 3' Surface Vertical Rod Push Bar Exit Device with Left Hand Reverse Lever Trim 613 Oil Rubbed Bronze Finish

$4,251.00

Von Duprin 8827L10B3RHR 3' Surface Vertical Rod Push Bar Exit Device with Right Hand Reverse Lever Trim 613 Oil Rubbed Bronze Finish

Von Duprin 8827L10B3RHR 3' Surface Vertical Rod Push Bar Exit Device with Right Hand Reverse Lever Trim 613 Oil Rubbed Bronze Finish

$4,251.00

Von Duprin 8827L26D3LHR 3' Surface Vertical Rod Push Bar Exit Device with Left Hand Reverse Lever Trim, 626 Satin Chrome Finish

Von Duprin 8827L26D3LHR 3' Surface Vertical Rod Push Bar Exit Device with Left Hand Reverse Lever Trim, 626 Satin Chrome Finish

$4,060.00

Von Duprin 8827L26D3RHR 3' Surface Vertical Rod Push Bar Exit Device with Right Hand Reverse Lever Trim, 626 Satin Chrome Finish

Von Duprin 8827L26D3RHR 3' Surface Vertical Rod Push Bar Exit Device with Right Hand Reverse Lever Trim, 626 Satin Chrome Finish

$4,060.00

Von Duprin 9875EO26D3 3' Mortise Smooth Case Exit Device, 626 Satin Chrome Finish

Von Duprin 9875EO26D3 3' Mortise Smooth Case Exit Device, 626 Satin Chrome Finish

$2,937.00

Was this resource helpful?

Your feedback helps us improve our technical resources and guides.

Customer Support

Terms of ServicePrivacy PolicyShipping & DeliveryReturns & RefundsAccessibilityDMCAFAQs

Copyright © 2026 US Made, LLC. All Rights Reserved.

All content is for informational purposes only and does not constitute professional, legal, or compliance advice. Verify all requirements with the applicable standards and authorities.

Secure Payments

VisaMastercardAmerican ExpressDiscoverApple PayGoogle PayShop PayPayPal