NFPA 1123: Code for Fireworks Display
What the outdoor display code actually requires for fire protection, why it names no fire extinguisher, and which states add one on their own authority
Last updated: August 24, 2026
Overview
NFPA 1123, Code for Fireworks Display, governs professional outdoor fireworks displays. NFPA describes it as containing information on how to set up and operate professional outdoor fireworks displays in order to prevent injuries to both the workers handling the fireworks and to the viewing audience, as well as to prevent fires that could cause property damage.
Section 1.1.1 states that the code applies to the construction, handling, and use of fireworks and equipment intended for outdoor fireworks display, and to the operation of the display. That application clause has been stable for about twenty years.
The current edition is 2026, with the next scheduled for 2030. The code is active and standalone, and it is maintained by NFPA's Technical Committee on Pyrotechnics. That committee assignment matters more than it sounds, because it is the reason this code and its indoor siblings diverge on the question most operators arrive with.
The Extinguisher Question
NFPA 1123 does not require fire extinguishers. It names no type, no rating, no quantity, and no placement. This is a deliberate committee decision rather than an oversight, and it has been reaffirmed twice in the current revision cycle. We sell fire extinguishers, and we are telling you the code does not require them here, because the alternative is helping you buy the wrong thing for the wrong reason.
The only mandatory fire protection provision in the code is a consultation. Section 8.1.1 reads: “The sponsor shall consult with the authority having jurisdiction, the local responding fire department (if different from the authority having jurisdiction), and the operator to determine the level of fire protection required.”
Extinguishers appear once, in Annex A, which the code itself states is not part of the requirements and is included for informational purposes only. The annex says fire protection could include portable fire extinguishers for the discharge area and standby fire apparatus for protection down range. That is guidance about what a conversation with the AHJ might produce, not a requirement.
Where the specs people remember actually come from
Many operators associate fireworks with a specific package: two pressurized water extinguishers plus two 10-B:C units. That package is real. It just belongs to the indoor documents. It is the requirement in NFPA 1126 for pyrotechnics before a proximate audience, and in NFPA 160 for flame effects. Both of those are written by the Technical Committee on Special Effects. NFPA 1123 belongs to the Technical Committee on Pyrotechnics, and the two families are intentionally different.
The committee was asked to add one, and said no
Mandatory extinguisher language was submitted six times as public input during the 2023 first draft stage, and again as public comments in 2024. Every submission was rejected. The committee's reasoning is worth reading, because it explains the design of the code:
- The requirements would be redundant to the consultation already required by Section 8.1.1, and could end up requiring more or less protection than a site actually needs
- Outdoor display sites vary enormously, and the committee specifically cited salt flats, beaches, and barges as examples where prescriptive equipment would not fit (our <ChakraLink as={Link} to="/resources/guides/fire-extinguishers-marine-facilities" color="navy" fontWeight="600">marina fire extinguisher guide</ChakraLink> covers the dock and barge environment)
- Prescriptive equipment can create a false sense of security where the protection provided is not adequate for the conditions but was supplied because the text asked for it
- The hazards indoors and outdoors are genuinely different, which is why NFPA 160 and NFPA 1126 are intentionally stricter
The committee was also blunt about the annex language, resolving that changes there “make it seem like fire extinguishers are required which is not the intent of the committee.”
The International Fire Code adds nothing either. A full-text review of IFC 2021 Chapter 56, the explosives and fireworks chapter covering Sections 5601 through 5609, contains no portable fire extinguisher provision, and no standby apparatus or fire department personnel provision. If someone cites an extinguisher requirement for an outdoor display in an IFC jurisdiction, it is coming from a state rule or a local permit condition.
Where States Add One Anyway
A state fire marshal can require what the standard does not, and at least one does. This is the practical answer for an operator: read your state rule and your permit conditions, not just the code the permit references.
California requires one. Title 19 of the California Code of Regulations, Section 1004(a), lists the tools required at the display site as, at a minimum, “a shovel, a serviceable pressurized water fire extinguisher, a bucket or other container to soak duds, and any other equipment as required by the authority having jurisdiction.” Read that carefully: it requires one unit, and it specifies no capacity and no UL rating. The commonly quoted “two 2.5 gallon” figure is not in the state rule.
That figure comes from local authorities stacking their own requirements on top. The City of Orange Fire Department, for example, requires “a minimum of two 2.5 gallon pressurized water fire extinguishers,” one in the storage area and one in the firing area, and states plainly that it is asking for this in addition to the requirements found in Title 19.
New York does not. The rule that adopts NFPA 1123 in New York, 12 NYCRR Part 61, contains no extinguisher, water, hose, apparatus, or standby requirement of its own. Adopting the code is the whole of it there.
The practical takeaway. Fire protection at an outdoor display is determined by the Section 8.1.1 consultation, by your state rule, and by your permit conditions, in that order of specificity. Ask the AHJ what it wants before the site plan is finalized, because the answer varies by state, by county, and by the site itself. A fire watch is a common outcome of that conversation. Note also that Section 5.1.6 keeps fire protection and emergency response personnel and their vehicles at or beyond the perimeter of the display site during the actual firing.
Display Site Radius
For aerial shells, Section 5.1.3.1 sets the minimum required radius of the display site at 70 feet per inch of the internal mortar diameter of the largest aerial shell to be fired. The largest device in the show sets the site size, and the underlying table has been stable across editions for roughly twenty years.
Internal mortar diameter, not shell diameter. This is the detail secondary sources get wrong most often, and permit documents are not immune. Both California AHJ documents reviewed for this page express the radius per inch of shell diameter instead, while simultaneously being stricter on the number at 100 feet per inch. The lesson is not that they are wrong to be stricter, which is their prerogative, but that you should read the units on whichever document governs your show rather than assuming they match the code.
Adoption by State
The current edition is 2026, but adopted editions in state rules run well behind it. Several states also adopt NFPA 1123 alongside its siblings while explicitly excluding others, so the family that applies to you is set by the adopting rule rather than by NFPA.
| State | Edition | Citation | Notes |
|---|---|---|---|
| Indiana | 2006 | 675 IAC 28-1-39 | Heavily amended. Excludes several referenced NFPA documents, names its own AHJ, and deletes or substitutes sections |
| New York | 2010 | 12 NYCRR 61-1.8 | Co-adopts NFPA 1126 (2011). No NFPA 160 |
| Washington | 2014 | WAC 212-17-021 | Co-adopts NFPA 1126 (2011) and NFPA 160 (2011) |
These are adopting instruments verified against primary state code text at the time of writing, and not a complete list of states. Editions change and local amendments sit on top of state adoption. Confirm the governing edition with your authority having jurisdiction.
Related Products
Since NFPA 1123 specifies no extinguisher, there is nothing to sell you on the strength of the code itself. What follows is for operators working under a rule that does require one, most commonly California's Title 19 requirement for a serviceable pressurized water fire extinguisher, or an AHJ condition that names units during the Section 8.1.1 consultation.
Pressurized water, for jurisdictions that require one
Water extinguishers have a temperature floor. NFPA 10 bars installing water-type extinguishers where temperatures fall outside 40°F to 120°F. Displays run in shoulder seasons and units often live in unheated storage between dates, so check the label range on the specific unit and plan storage accordingly.
Buying in volume?
Volume pricing on bulk orders. Typical turnaround: one business day. Quotes typically returned within one business day.
or call 714-248-6555 · email partners@usmadesupply.com
Frequently Asked Questions
Does NFPA 1123 require fire extinguishers at a fireworks display?
No. This is the most common misconception about the code. NFPA 1123 contains no mandatory extinguisher provision. Its only fire protection requirement is Section 8.1.1, which says the sponsor shall consult with the authority having jurisdiction, the local responding fire department, and the operator to determine the level of fire protection required. Extinguishers appear only in Annex A, which the code itself states is not part of the requirements and is included for informational purposes only.
Why do people think NFPA 1123 requires two water and two 10-B:C extinguishers?
Because that package is real, but it belongs to the indoor standards rather than to NFPA 1123. Two pressurized water units at minimum 2-A plus two at minimum <ChakraLink as={Link} to="/resources/guides/class-b-fire-extinguisher-guide" color="navy" fontWeight="600">10-B:C</ChakraLink> is the requirement in NFPA 1126 for pyrotechnics before a proximate audience and in NFPA 160 for flame effects. Those two documents are written by NFPA’s Technical Committee on Special Effects. NFPA 1123 is written by the Technical Committee on Pyrotechnics, and it deliberately does not carry that clause.
Did anyone try to add an extinguisher requirement to NFPA 1123?
Yes, repeatedly, and the committee rejected it every time. Mandatory extinguisher language was submitted six times as public input during the 2023 first draft stage and again as public comments in 2024. The committee’s stated reasoning was that the requirements would be redundant to the consultation already required by Section 8.1.1, that outdoor display sites vary too much (it cited salt flats, beaches, and barges), and that prescriptive equipment could give a false sense of security if it were not adequate for the actual conditions.
Does the International Fire Code require extinguishers at a fireworks display?
No. A full-text review of IFC 2021 Chapter 56, the explosives and fireworks chapter covering Sections 5601 through 5609, found no portable fire extinguisher provision at all, and no standby apparatus or fire department personnel provision either. If you are working in an IFC jurisdiction and someone cites an extinguisher requirement for a display, it is coming from a state rule or a local permit condition rather than from Chapter 56.
Which states require a fire extinguisher at a display anyway?
California does, by its own rule rather than through the standard. Title 19 CCR Section 1004(a) lists the tools required at a display site as, at a minimum, a shovel, a serviceable pressurized water fire extinguisher, a bucket or other container to soak duds, and any other equipment required by the authority having jurisdiction. Note that it requires one unit and specifies no capacity and no UL rating. New York, by contrast, adopts NFPA 1123 without adding any extinguisher, water, hose, apparatus, or standby requirement of its own.
How is the display site radius calculated?
For aerial shells the minimum required radius of the display site is 70 feet per inch of the internal mortar diameter of the largest shell to be fired. Note that it keys on internal mortar diameter, not shell diameter, which secondary sources and even some permit documents get wrong. The largest device in the show sets the site size, and the figures have been stable across editions for about twenty years.
What edition of NFPA 1123 applies to my display?
Whichever your jurisdiction adopted, which is rarely the current one. The current edition is 2026, with the next scheduled for 2030. Adopted editions found in state rules include 2006 in Indiana, 2010 in New York, and 2014 in Washington. Indiana also amends heavily, excluding several referenced NFPA documents, naming its own authority having jurisdiction, and deleting or substituting sections outright.
Was this resource helpful?
Your feedback helps us improve our technical resources and guides.
